Revision of National Environment Standards 2020

Incinerator Emission Standards 2020

Solid Waste Sampling duration (mnts, unless otherwise stated)
> Particulates: 50mg/Nm3 (Half hourly average)
> HCl: 50 mg/Nm3 (Half hourly average)
> SO2: 200mg/Nm3 (Half hourly average)
> CO: 100mg/Nm3 (Half hourly average)
> Total Organic Carbon: 20mg/Nm3 (Half hourly average)
> HF: 4 mg/Nm3 (Half hourly average)
> NOx (NO and NO2 expressed
 as NO2) : 400mg/Nm3 (Half hourly average)
> Total dioxins and furans : 0.1 ng TED/Nm3 (6-8 hours)
> Cd + Th + their compounds : 0.05mg/Nm3 (Anywhere between 30 minutes and 8 hours)
> Hg and its compounds : 0.05 mg/Nm3(Anywhere between 30 minutes and 8 hours)
> Sb + As + Pb + Cr + Co + Cu + Mn + Ni + V + their compounds : 0.5mg/Nm3 (Anywhere between 30 minutes and 8 hours)

Bio-medical Waste Sampling duration (mnts, unless otherwise stated)
> Particulates: 50mg/Nm3 (30 or 1NM3 of sample volume, whichever is more )
> HCl: 50 mg/Nm3 (30 or 1NM3 of sample volume, whichever is more )
> NOx (NO and NO2 expressed
 as NO2) : 400mg/Nm3 (30 for online sampling or grab sample)
> Total dioxins and furans : 0.1 ng TED/Nm3 (8 hours or 5NM3 of sample volume, whichever is more)
> Hg and its compounds : 0.05 mg/Nm3 (2 hours or 1NM3 of sample volume, whichever is more)

Hazardous waste sampling duration (mnts, unless otherwise stated)
> Particulates: 50mg/Nm3 (30)
> HCl: 50 mg/Nm3 (30)
> SO2: 200mg/Nm3 (30)
> CO: 100mg/Nm3 (30)
> Total Organic Carbon: 20mg/Nm3 (24 hours)
> HF: 4 mg/Nm3 (30)
> NOx (NO and NO2 expressed as NO2) : 400mg/Nm3 (30)
> Total dioxins and furans : 0.1 ng TED/Nm3 (30)
> Cd + Th + their compounds : 0.05mg/Nm3 (8 hours)
> Hg and its compounds : 0.05 mg/Nm3 (2hours)
> Sb + As + Pb + Cr + Co + Cu + Mn + Ni + V + their compounds : 0.5mg/Nm3 (2 hours)

Close Menu